a) limits to be set for disturbance emission into industrial power supply systems (including the planning levels defined in 3.1.5);
NOTE 1 A very wide range of conditions is possible in the electromagnetic environments of industrial and other non-public networks. These are approximated in this standard by the three classes described in Clause 4. However, it is the responsibility of the operator of such a network to take account of the particular electromagnetic and economic conditions, including equipment characteristics, in setting the above-mentioned limits.
- b) the choice of immunity levels for the equipment within these systems.
- — voltage deviations;
- — voltage dips and short interruptions;
- — voltage unbalance;
- — power-frequency variations;
- — harmonics up to order 50;
- — interharmonics up to the 50th harmonic;
- — voltage components at higher frequencies (above 50th harmonic);
- — d.c. component;
- — transient overvoltages.
NOTE 2 Compatibility levels at the point of common coupling (PCC) on public networks are specified in IEC 61000‑2‑2 for low-voltage networks and IEC 61000‑2‑12 for medium-voltage networks. Technical reports IEC 61000‑3‑6 and IEC 61000‑3‑7 describe the approach of supply authorities to the limitation of emissions from installations and large loads.