loading preview...
summary
Safety of transformers, reactors, power supply units and similar products for supply voltages up to 1100 V. Particular requirements and tests for auto transformers and power supply units incorporating auto transformers | Status: Current, Superseded, Under review
description
1 Scope
Replacement:
This part of IEC 61558 deals with the safety of auto transformers for general applications and power supply units incorporating auto transformers for general applications. Transformers incorporating electronic circuits are also covered by this standard.
NOTE 1 Safety includes electrical, thermal and mechanical aspects.
Unless otherwise specified, from here onward, the term transformer covers auto transformers for general applications and power supply units incorporating auto transformers for general applications.NOTE 2 : For power supply units (linear) this part is applicable. For switch mode power supply units,IEC 61558‑2‑16 is applicable together with this part.
This part is applicable to stationary or portable, single-phase or polyphase, air-cooled (natural or forced) independent or associated dry- type transformers. The windings may be encapsulated or non-encapsulated. The rated supply voltage does not exceed 1 100 V a.c., and the rated supply frequency and the internal operating frequencies do not exceed 500 Hz. The core power does not exceed:- — 2 kVA for single-phase transformers;
- — 10 kVA for polyphase transformers.
- — 40 kVA for single-phase transformers;
- — 200 kVA for polyphase transformers.
NOTE 3 Attention is drawn to the following:
- — for transformers intended to be used in vehicles, on board ships, and aircraft, additional requirements (from other applicable standards, national rules, etc.) may be necessary;
- — measures to protect the enclosure and the components inside the enclosure against external influences such as fungus, vermin, termites, solar-radiation, and icing should also be considered;
- — the different conditions for transportation, storage, and operation of the transformers should also be considered;
- — additional requirements in accordance with other appropriate standards and national rules may be applicable to transformers intended for use in special environments.
NOTE 4 Future technological development of transformers may necessitate a need to increase the upper limit of the frequencies, until then this part may be used as a guidance document.